Skip to content
IAIRCON

BOOK OR CHAT

Book a service

Repairs & error codes

Panasonic aircon error codes: the full H and F code list

By Eric Lim, founder of iAircon.Repair · · 8 min read

Why is my Panasonic aircon timer light blinking?

A blinking TIMER lamp on a Panasonic aircon means the unit has stopped and stored an error code. Read it with the remote: hold the CHECK button for five seconds, then press the timer up or down button until the unit beeps. The H or F code on the remote at that beep is the stored fault.

Key takeaways

  • The TIMER lamp is the warning: blinking with the unit stopped means a code is stored.
  • CHECK reads it: the recessed CHECK button and the timer buttons find the code in a minute or two.
  • H codes point to a part, F codes to a protection: F codes mean the outdoor unit or the gas circuit kept tripping a safety limit.
  • Gas and compressor codes mean stop: F91, F93, F97, F98 and F99 can damage the compressor if the aircon keeps running.

Not every blinking light is a fault. A POWER lamp that blinks before the unit switches on means an ON timer is getting ready, and a TIMER lamp that stays lit means a daily timer is set. Both are normal.

How do I read a Panasonic error code with the remote?

This is Panasonic's self-diagnosis, and it works the same way on the Panasonic wall-mounted and multi-split remotes sold in Singapore. Read the code before you switch anything off: Panasonic notes the stored code can be lost after a power cut.

  1. Point the remote at the indoor unit, as you would to switch it on.
  2. Press and hold CHECK for five seconds. It is a small recessed button, so use a pen tip or a pin. The remote shows "- -".
  3. Press the timer up or down button, one press at a time. The first code is H00, and each press sends the next code to the unit.
  4. Watch and listen after every press. When the code matches, the indoor unit beeps for about four seconds and its POWER lamp lights. When it does not match, there is no beep.
  5. Write the code down or take a photo of the remote screen.
  6. Hold CHECK for five seconds again to leave check mode.

A few codes let the unit keep cooling at reduced power, so it can still run while you wait for a technician. In that state it answers the remote with four beeps instead of one. Wi-Fi models with the Comfort Cloud app also show the code in the app.

Panasonic error code list

This list follows Panasonic's own error code table and its service manuals for home wall-mounted units and System 2, 3 and 4 multi-splits, in our own words. Panasonic warns that some codes may not apply to your model. We left out codes for heating, ventilation and water equipment that homes in Singapore do not use.

"Reset once" means: switch the aircon off at its isolator, wait three minutes, switch it on. "Off" means leave the aircon switched off until it is checked.

H00: no fault

Code

What it means

What you can do

H00

No fault stored

Reset once; call us if the lamp keeps blinking

Indoor unit codes

Code

What it means

What you can do

H14

Room (air intake) temperature sensor fault

Technician

H19

Indoor fan motor locked or not turning

Off, technician

H23

Indoor coil temperature sensor fault

Technician; reduced cooling may still run

H24

Indoor coil temperature sensor 2 fault

Technician

H52

Left-right louver limit switch fault

Technician

H70

Light sensor fault

Technician

H99

Freeze protection: the indoor coil got too cold, often from dirty filters or a dirty unit

Wash the filters; technician if it returns

Outdoor unit codes

Code

What it means

What you can do

H15

Compressor temperature sensor fault

Technician

H16

Outdoor current sensor fault

Off, technician

H17

Outdoor suction temperature sensor fault

Technician

H27

Outdoor air temperature sensor fault

Technician; reduced cooling may still run

H28

Outdoor coil temperature sensor fault

Technician; reduced cooling may still run

H30

Discharge pipe temperature sensor fault

Technician

H32

Outdoor coil temperature sensor 2 fault

Technician

H34

Heat sink temperature sensor fault

Technician

H36

Outdoor gas pipe temperature sensor fault

Technician

H37

Outdoor liquid pipe temperature sensor fault

Technician

H64

High pressure sensor fault

Off, technician

H71

Cooling fan inside the control board fault

Technician

H97

Outdoor fan motor locked or not turning

Off, technician

Wiring, matching and multi-split codes

Code

What it means

What you can do

H11

Indoor and outdoor units cannot talk to each other

Reset once; technician if it returns

H12

The indoor units do not match the outdoor unit's capacity (multi-split)

Technician

H33

Indoor and outdoor units connected wrongly (different rated voltages)

Technician

H38

Indoor and outdoor units do not match (brand code)

Technician

H39

A room that is off or on standby is still running, often crossed wiring or piping, or an expansion valve fault (multi-split)

Technician

H41

Wiring or piping connected to the wrong room (multi-split)

Technician

F17

A room on standby is freezing up, often a leaking expansion valve (multi-split)

Off, technician

Feature codes: Wi-Fi, nanoe, ion and ECONAVI

These belong to an extra feature, not the cooling itself.

Code

What it means

What you can do

H25

Ion device fault (models with one)

Technician

H26

Minus ion fault (models with one)

Technician

H59

ECONAVI sensor fault (models with ECONAVI)

Technician

H67

nanoe fault (models with nanoe)

Technician

H79

Wi-Fi module write error

Technician

H85

Indoor unit cannot talk to the Wi-Fi module

Technician

F codes: protection that kept tripping

An F code usually means a protection tripped several times in a short spell. Below that count, the unit protects itself and restarts on its own.

Code

What it means

What you can do

F11

Cooling-only models: indoor coil or room temperature sensor fault (heat pump models: four-way valve)

Technician

F16

Total running current too high

Off, technician

F87

Control box overheated

Off, technician

F90

Outdoor board power circuit protection, or the board cannot talk to the compressor control

Off, technician

F91

Refrigerant circuit fault: low gas, or a valve left closed

Off, gas check

F93

Compressor not turning at the right speed, or locked

Off, technician

F94

Compressor discharge pressure too high

Off, technician

F95

High pressure in cooling: the gas circuit or the outdoor unit's airflow

Off, technician

F96

Outdoor power module overheated

Off, technician

F97

Compressor overheated, often low gas

Off, gas check

F98

Total running current too high

Off, technician

F99

Outdoor DC current peak: power module fault or compressor locked

Off, technician

Your code is not here, or the lamp is blinking right now? Message Luna on WhatsApp with the code and your model number, which is on a sticker on the side of the indoor unit, and we will tell you the next step.

Which Panasonic codes need attention first?

Some codes are worth acting on the same day:

  • F91 and F97, gas. Both often mean the system is short of refrigerant. The circuit is sealed, so low gas means a leak somewhere, and topping up without finding it only buys time; our post on aircon gas leak signs explains why.
  • H99, freeze-up. Usually airflow: clogged filters, a dirty coil or a blower fan caked with dust. Washing the filters is the first step. A thorough clean such as our premium servicing with PowerJet often clears it; see what a Panasonic inverter chemical wash removes from a unit like this.
  • H19 and H97, fans. A fan that has stopped means the coil cannot shed its heat or cold, so keep the aircon off.
  • H11, wiring. Can be a loose or damaged cable between the units, a power problem or a board fault. One reset is fine; if it returns, it needs testing on site.

Why one room or every room?

On a System 2, 3 or 4, several indoor units share one outdoor unit. An indoor code such as H19 or H99 belongs to that one room. Outdoor and F codes, such as H97, F91 or F97, usually stop every room on that outdoor unit, because they all depend on it. H12, H39, H41 and F17 only appear on multi-split systems.

Can I reset a blinking Panasonic aircon myself?

You can try once, for the codes the list marks "Reset once". Read and note the code first, because a power cut can wipe it. Then switch the aircon off at the isolator switch, wait three minutes and switch it back on.

If the fault was a one-off, such as a brief power dip, the unit may run normally. If the same code returns, the fault is real. Resetting it over and over hides the symptom while the cause gets worse, for example a compressor running short of gas.

What it costs

The cost depends on what the code points to. We diagnose first and only replace what has failed.

Job

Price

What drives it

Fault diagnosis visit

S$150 per visit

Flat fee per visit; parts and repair extra

Gas Check + Top-up (F91, F97)

S$165

Paid at booking; goes towards the fix if the gas turns out fine

Gas leak repair and recharge

Leak check from S$580 (gas top-up included), repair quoted after

Leak location, refrigerant type (R32 or R410A), evacuation

Board, sensor, fan motor or compressor

Quoted after the S$150 diagnosis

The part for your model

Repairs carry our warranty from 180 days.

When to call a technician

Call us if:

  • the same code comes back after one reset
  • the code is an F code, or points to a fan, the compressor or a circuit board
  • the unit is not cooling, is leaking water, or is making new noises along with the blinking
  • the code is one you cannot find, or the beep is hard to make out

Other brands blink and beep their own way: see our lists of Daikin error codes and Mitsubishi Electric blinking lights. Send us the code when you get in touch; it helps us bring the right parts and tools for aircon repair and troubleshooting. You can book online in under a minute, or message Luna, our AI assistant, on WhatsApp at any hour.

Frequently asked questions

Where is the CHECK button on a Panasonic remote?

It is a small recessed button marked CHECK, set into the remote so it cannot be pressed by accident. Use a pen tip or a pin. On some remotes it sits under a sliding cover; if you cannot find it, the remote's manual shows where it is.

Why is the POWER light blinking but the aircon is not on?

That is normal. Panasonic units blink the POWER lamp while they prepare to switch on for an ON timer. A fault shows on the TIMER lamp instead, and the unit stops.

What does H99 mean on a Panasonic aircon?

H99 is freeze protection: the indoor coil got too cold and the unit stopped to protect itself. Panasonic links it to dirty filters, a dirty unit and blocked airflow. Wash the filters first; if it comes back, the coil and blower fan need a proper clean.

Does F91 mean my Panasonic aircon is leaking gas?

F91 means the refrigerant circuit is not working as it should, most often low gas, or a valve left closed after an installation. The circuit is sealed, so low gas on a unit that has been running for years usually means a leak. Book a gas check rather than a top-up alone.

Do Daikin and Mitsubishi Electric use the same codes as Panasonic?

No. Each brand has its own codes and its own way of reading them, and the same letters can mean different things. Use this list only for Panasonic units.

Is it safe to keep using a Panasonic aircon while the timer light blinks?

If the unit has stopped, switch it off and leave it off until it is checked. Restarting it again and again can strain the compressor, especially when the code points to gas, the compressor or a fan that is not turning.

Found this useful? Share it

Follow Uncle Eric for more real jobs

Eric Lim, aka Uncle EricFounder of iAircon.Repair, now in its 10th year servicing aircons in Singapore. Some of our jobs are filmed, and you can watch the work on YouTube.

Keep reading