What does a blinking light on a Mitsubishi Electric aircon mean?
A blinking operation lamp on a Mitsubishi Electric Starmex means the unit found a fault and stopped. Count the blinks between the pauses: each count points to an area, such as 2 for a temperature sensor, 3 for the indoor fan motor and 5 for the outdoor unit's power system. A technician confirms the part.
Key takeaways
- Count the blinks: the lamp blinks a set number of times, pauses for about two and a half seconds, and repeats.
- Low counts are indoor, 5 and up are outdoor: 2 to 4 blinks point to the indoor unit, 5 to 7 and 14 to the outdoor unit.
- All lamps blinking together is the vane: the flap at the air outlet is not seated, so both units stop.
- Outdoor power and gas faults mean stop: 5 blinks, 14 blinks and codes such as PL or UP can damage the compressor if the aircon keeps running.
In the video above, a Mitsubishi Electric Starmex System 3 (outdoor unit MXY3G28VA) at Ashi Foot Reflexology in Katong was reported blinking by the staff. We counted 7 blinks, which points to the outdoor circuit board. We checked the control board, and further troubleshooting traced the fault to a failed relay; we replaced it with an original Mitsubishi Electric part. Read the full Katong repair.
How do I read the blinks?
- Stand in front of the indoor unit and look at the operation lamp: the upper lamp, or the left one on some models.
- Count the blinks. The lamp blinks quickly a set number of times, goes off for about two and a half seconds, then repeats.
- Count at least two rounds to be sure of the number.
- Check the pattern: a steady blink with no pause, or every lamp blinking together, means something different from a count.
- Write down the count and the model number, which is on a sticker on the side of the indoor unit.
- Switch the aircon off and find the count in the list below.
Mitsubishi Electric blinking light list
This list follows Mitsubishi Electric Singapore's own error code sheet and the Starmex service manuals, in our own words. It is for Starmex inverter indoor units, on a single split or a System 2, 3 or 4 multi-split. Older or other series can differ slightly, so treat each row as a guide to where the fault sits, not a diagnosis.
"Reset once" means: switch the aircon off at its isolator, wait three minutes, switch it on. "Off" means leave the aircon switched off until it is checked.
Starmex inverter units
Operation lamp | What it means | What you can do |
|---|---|---|
Blinks steadily, no pause | No signal from the outdoor unit for 6 minutes: wiring between the units, or the outdoor unit has no power | Reset once; technician if it returns |
2 blinks | Indoor coil or room temperature sensor fault | Technician |
3 blinks | Indoor fan motor fault: the motor is not reporting that it turns | Off, technician |
4 blinks | Indoor circuit board fault | Off, technician |
5 blinks | Outdoor power system: the compressor stopped three times for too much current or a failed start | Off, technician |
6 blinks | Outdoor temperature sensor fault | Technician |
7 blinks | Outdoor circuit board fault | Off, technician |
14 or more blinks | Other outdoor fault, for example a valve not fully open | Off, technician |
Lamp lit, outdoor unit not running | Outdoor control fault | Off, technician |
All lamps blink together | The horizontal vane (the flap at the air outlet) is not seated | Switch off and on; technician if it returns |
Older non-inverter units
Older non-inverter Starmex models use a shorter table: 2 blinks for a temperature sensor, 3 for the indoor fan motor and 4 for the indoor circuit board, as above. 14 blinks means a refrigerant circuit fault, such as low gas or an outdoor fan that has locked. Leave it off until it is checked.
Remotes with a CHECK button: two-digit codes
Some Mitsubishi Electric remotes have a small CHECK button. Switch the remote off, stand within two metres of the indoor unit, point the remote at it and hold CHECK with a pen tip until the unit beeps and a code shows on the remote. "00" means no fault; "-" means the remote got no reply, so move closer and try again. Press any button to leave. Many Starmex remotes sold in Singapore have no CHECK button; on those, use the blink count.
Code | What it means | What you can do |
|---|---|---|
00 | No fault | Reset once; call us if the lamp keeps blinking |
E6 / E7 | Signal problem between the indoor and outdoor units | Reset once; technician if it returns |
E8 / E9 / EC | The outdoor unit is not receiving the indoor unit's signal | Reset once; technician if it returns |
Fb | Indoor control system fault | Off, technician |
Pb | Indoor fan motor fault | Off, technician |
P1 | Room temperature sensor fault | Technician |
P2 / P9 | Indoor coil temperature sensor fault | Technician |
FC | Outdoor board memory fault | Off, technician |
Fd | Wrong supply voltage | Off, technician |
P8 | Pipe temperature fault | Off, technician |
PL | Outdoor refrigerant circuit fault | Off, gas check |
U3 | Discharge temperature sensor fault | Technician |
U4 | Outdoor sensor fault: heat sink, board, outdoor air or outdoor coil | Technician |
UE | Stop valve closed | Off, technician |
UP | Outdoor power system fault | Off, technician |
Outdoor board lights, for technicians
On System 2, 3 and 4 outdoor units (MXY), the outdoor circuit board has a red and a yellow LED. Both lit steadily means the outdoor unit sees no fault; blink patterns tell a technician which part to test. Mitsubishi Electric Singapore's sheet above has the full LED table. Owners should not open the outdoor unit: the board carries mains power.
Your pattern is not here, or the lamp is blinking right now? Message Luna on WhatsApp with the blink count and your model number, and we will tell you the next step.
How we trace a blinking Starmex
The blink count tells us where to start, not which part to buy. We confirm the area with the count, test the parts there, and only then order an original part. On the Katong job in the video, 7 blinks sent us to the outdoor boards, and testing there found the failed relay before anything was ordered; the replacement took about three hours. For how these units are built, read our technician's view of Mitsubishi Electric Starmex.
Why one room or every room?
On a System 2, 3 or 4, several indoor units share one outdoor unit. Two to four blinks belong to that one room. Five to seven blinks, 14 blinks and the steady blink usually stop every room on that outdoor unit, because they all depend on it.
Can I reset a blinking Mitsubishi aircon myself?
You can try once, for the patterns the list marks "Reset once". Count the blinks first, so you still have them if the lamp goes off. Then switch the aircon off at the isolator switch, wait three minutes and switch it back on.
If the fault was a one-off, such as a brief power dip, the unit may run normally. If the same blinks return, the fault is real. Resetting it over and over hides the symptom while the cause gets worse, for example a compressor running short of gas; our post on aircon gas leak signs explains why low gas always means a leak somewhere.
What it costs
The cost depends on what the blinks point to. We diagnose first and only replace what has failed.
Job | Price | What drives it |
|---|---|---|
Fault diagnosis visit | S$150 per visit | Flat fee per visit; parts and repair extra |
Gas Check + Top-up (PL, 14 blinks on older units) | S$165 | Paid at booking; goes towards the fix if the gas turns out fine |
Gas leak repair and recharge | Leak check from S$580 (gas top-up included), repair quoted after | Leak location, refrigerant type (R32 or R410A), evacuation |
Board, sensor, fan motor or compressor | Quoted after the S$150 diagnosis | The part for your model |
Repairs carry our warranty from 180 days.
When to call a technician
Call us if:
- the same blinks come back after one reset
- the count is 3 or more, or the remote shows a code marked "Off" above
- the unit is not cooling, is leaking water, or is making new noises along with the blinking
- you cannot make out the count
Other brands blink their own way: see our lists of Daikin error codes and Panasonic error codes. Tell us the blink count when you get in touch; it helps us bring the right parts and tools for aircon repair and troubleshooting. You can book online in under a minute, or message Luna, our AI assistant, on WhatsApp at any hour.
Frequently asked questions
What does 3 blinks mean on a Mitsubishi Starmex?
Three blinks of the operation lamp on a Starmex inverter indoor unit means the indoor fan motor is not reporting that it turns: the motor, its wiring or the indoor board. Keep the aircon off until it is checked.
What does 5 blinks mean on a Mitsubishi aircon?
Five blinks point to the outdoor unit's power system: the compressor stopped three times in a row because of too much current or a failed start. It can be the compressor, the outdoor board or a valve left closed, so leave the aircon off.
Why are all the lights blinking on my Mitsubishi aircon?
When every lamp blinks together, the horizontal vane, the flap at the air outlet, is not seated properly, and both units stop. Switch off, and call us if it happens again after switching back on.
Does a Mitsubishi Electric remote show the error code?
Only remotes with a small CHECK button show a two-digit code, such as P1 or U3. Many Starmex remotes sold in Singapore have no CHECK button; on those, the blink count on the indoor unit is the code.
Do Mitsubishi Heavy Industries aircons use the same blinks?
No. Mitsubishi Electric (Starmex) and Mitsubishi Heavy Industries are different companies with different codes. This list is for Mitsubishi Electric only.
Is it safe to keep using a Mitsubishi aircon while the lamp blinks?
If the unit has stopped, switch it off and leave it off until it is checked. Restarting it again and again can strain the compressor, especially when the blinks point to the outdoor power system or the gas circuit.